Pre-installation Guidelines SIMATIC 545/555/575 System Manual
575 Fault Relay Operation (continued)
To use the fault relay to control the power to the electronic control system,
you must wire the relay so that it controls the interposing relays in the
supply line. An example of this is shown in Figure 2-6.
NOTE: Figure 2-6 is not a complete electrical diagram. It is for illustration
purposes only. A qualified control engineer should be aware of any relevant
regulations and design the system with these in mind.
FLT
CRM
CRM
Master Stop
PB
Master Start
PB
F1
F2
F3 F4 F5
P/S
C
P
U
C
P
U
C
P
U
FLT
CRM
Output
Modules
575 VME System
L1
L2
24V115V
TDR
TDR
CRM
Figure 2-6 Safety Chain Controlling Control System Power Example
In Figure 2-6, relay CRM is the interposing relay, and FLT is a 24-volt relay
in the low-voltage safety chain. TDR is a delay-on relay with normally
closed contacts. Note the use of pushbutton switches for master stop
(normally closed) and master start (normally open). Power to the control
system is applied when the master start switch is actuated. If the
time-delay relay opens before the fault relay is closed, then the control
system loses power. If either the master stop switch is actuated or one of the
fault relays opens, then the control system is turned off.