2-7
SIMATIC 545/555/575 System Manual
Pre-installation Guidelines
Power-up Reset
Power-off
AUX 11 or
AUX 12
restart
Non-fault
575 CPU
initialization
Fault Detected
Fault
Detected
FAULT
mode
Power-off
(open)
FAULT
IDLE
(open)
(closed)
NORMAL
Figure 2-4 Software State Diagram
Fault State
The fault relay opens whenever the 575 CPU enters the FAULT mode or
loses power. To close the fault relay after entering FAULT mode, transition
the 575 CPU to PROGRAM mode either by executing an AUX 11 or AUX 12
from TISOFT, or by performing a bad-battery power cycle.
NOTE: If a hardware watchdog timeout sends the CPU into FAULT mode
(WDG LED is illuminated) when the 575 is configured as
USER-CONFIGURED
and DO NOT ASSERT/WAIT FOR SYSRESET* (in other words, SW5 on the I/O
annex card is set to the Off position), the following procedure must be
followed to re-enable the fault relay:
Execute a power cycle. After the power cycle, the 575 system is still in
FAULT mode and the fault relay on each of the 5752104 CPUs in the
system is open.
Execute AUX 11 or AUX 12 from TISOFT. The 575 CPUs are now in
PROGRAM mode and the fault relay on each of the 575 CPUs in the
system is closed.