T400 Controller Facilities Manual
667/EB/20200/000 Page 2-8 Issue 9
Each stream will then move immediately to its individual switch off stage subject to
any delays caused by minimum greens or intergreens timing off and also subject to any
stage movement restrictions.
When all streams have reached their switch-off stages and all minimum greens have
expired then all signals will be extinguished.
The Part Time switch off stage for each stream is specified in configuration.
2.6.4(i) Start Up
The start-up stage for each stream is configurable. This determines the stages that the
controller starts up in when powering up, when coming out of Part Time, or after the
signals have been switched off from Special Conditioning (using the method that
implements start-up).
2.6.5 Window Timers
(See also section 3.7.4)
Provision has been made within the software to provide 4 separate window timers, one
for each stream. This is necessary because up to 4 stages may be running
simultaneously, each demanding a different window time. Each window timer will run
the window time related to the stage within its associated stream. This is associated
with type 3 phases.
2.6.6 Extend all Red (Hold Intergreen)
(See also section 7)
There is an extend all red Facility available on each stream. There is a separate All Red
Extension time and All Red Maximum time for each stream. If the extend all red input
is active on the specified stage to stage movement, then when the first phase in the
stream that is about to go to green reaches the start of its red-green transition period,
the intergreen and delay times concerned with the intergreen are held until the All Red
extension period terminates or the All Red Maximum time is reached. (See also section
19.2).
Each stream’s all red extension time may be accessed using the handset command:
REX followed by the stream number (e.g. REX1)
Each stream’s all red maximum time may be accessed using the handset command:
RMX followed by the stream number (e.g. RMX2)
2.6.7 LMU Supplementary Intergreen Extensions
There is an LMU supplementary intergreen extension facility available for each stream.
If an LMU indicates one red lamp fail (see Section 19.2) then the all red period of the