T400 Controller Facilities Manual
667/EB/20200/000 Page 9-17 Issue 9
The above conditions may not cause UTC mode to become the current mode due to
the mode priority structure. UTC may be active without being the current mode and
certain control bits may have an influence in the current mode.
Conditions (i) or (ii) will cause the UTC ACTIVE indicator on the manual panel to be
illuminated.
9.3.9 Outstation Transmission Units (OTU)
See Figure 21.14.
Some UTC systems require all control and reply signals to be inverted by an
interposing unit.
9.3.10 The Effects of U.T.C. Control Bits on C.L.F. and Master Time Clock
The master time clock
introduces C.L.F. Plans
dependent upon the entries
in its timetable.
The method of Plan
introduction may be either
of two options.
MASTER TIME CLOCK
(REAL TIME CLOCK)
----------------->
C.L.F.
CABLELESS LINK
FACILITY
UTC bits which affect MTC
TS: Resets Real Time Clock to a
configured value, e.g. 1.00 a.m.
OR
TS1: Resets real time clock to time and
30 seconds if within +29 seconds of
time when synch received. Synch is
only applicable at the following minutes
past the hour: 8, 18, 28, 38, 48, 58.
UTC bits which affect C.L.F.
SG: Resets CLF. Plan to start of
Group 0
(N.B. This bit must not be used in
conjunction with the 2nd option for
plan introduction otherwise synchron-
isation may be upset.)
9.3.10(a) Options
Option 1
When the timetable introduces the plan, the plan always starts at Group 0.
Option 2
When a plan is introduced the controller calculates what group should be running
based upon the Plan being introduced at 2.00 am and the time elapsed between 2.00