15
Engineer programming via the browser
Configuring controller inputs & outputs
186
Siemens AB
A6V10276959
Security Products
18.11.2011
See also
Calendars [236]
15.9.2.1 Outputs types and output ports
Each output type can be assigned to one of the 6 physical output ports on the SPC
controller or to an output on one of the connected expanders. Output types that are
not assigned to physical outputs act as indicators of events on the system and may
be logged and/or reported to remote central stations if required.
The output ports on the expanders are all single pole relay type outputs (NO, COM,
NC); therefore, output devices may need external power sources to activate if they
are wired to expander outputs.
The activation of a particular output type depends on the zone type (see page [➙
284]) or alert condition that triggered the activation. If multiple areas are defined on
the system then the outputs on the SPC are grouped into system outputs and area
outputs; the system outputs are activated to indicate a system wide event (e.g.
mains fault) whereas the area outputs indicate events detected in one or more of
the defined areas on the system. Each area has its own set of area outputs; if the
area is a common area for other areas, then its outputs will indicate the state of all
the areas it is common for, including its own state. For example, if Area 1 is
common for Area 2 and 3, and Area 2 Ext. Bell is active, then the Area 1 Ext Bell
output is also active.
Some output types can only indicate system wide events (no specific area
events). Please refer to the table below for further information.
Output Type
Description
External Bell
This output type is used to activate the system external bell and is active when any
Area External Bell is active. By default, this output is assigned to the first output on the
controller board (EXT+, EXT-).
Note: An external bell output is automatically activated whenever a zone programmed
as an Alarm zone triggers an alarm in Fullset or Partset modes.
External Bell Strobe
This output type is used to activate the strobe on the system external bell and is active
when any area strobe is active. By default, this output is assigned to the strobe relay
output (Output 3) on the Controller board (NO, COM, NC).
Note: An external bell strobe output is automatically activated whenever a zone
programmed as an alarm zone triggers an alarm in Fullset or Partset modes. The
external bell strobe activates on a ’Fail to Set’ condition if the strobe on the ’Fail to Set’
option is checked in system options.
Internal Bell
This output type is used to activate the internal bell and is active when any area
Internal Bell is active. By default, this output is assigned to the second output on the
controller board (INT+, INT-).
Note: An internal bell output is automatically activated whenever a zone programmed
as an Alarm zone type triggers an alarm in Fullset or Partset modes. The internal Bell
activates on a ’Fail to Set’ condition if the Bell on the ’Fail to Set’ option is checked in
system options.
Alarm
This output turns on following alarm zone activation on the system or from any area
defined on the system.
Alarm Confirmed
This output turns on when an alarm has been confirmed. An alarm is confirmed when 2
independent zones on the system (or within the same Area) activate within a set time
period).