Engineer programming via the browser
Configuring communications
216
Siemens AB
A6V10276959
Security Products
18.11.2011
Answer Mode
The modem can be programmed to answer calls based on the following conditions:
Don’t answer calls: Modem never answers calls.
Answer after ‘x’ rings: Select the number of rings after which the modem
answers the incoming call.
Confirm party / Hang-up mode: In this mode of operation the calling party calls
the modem, hangs up after 1 ring burst only and then immediately re-calls the
modem. The SPC system knows to automatically answer the call in this
condition.
Prefix
Enter the number required to access a line. (e.g. if connected to a PBX)
Line Monitoring
Enable this feature to monitor the voltage of the line connected to the modem.
Note : EN 50131-9 Confirmation configuration
In order for EN50131-9 Confirmation to operate correctly, line monitoring must be
enabled. (refer to System Options [➙ 154])
Monitor Timer
Select the period (in seconds) for which the line voltage must be seen as being
incorrect before the line is deemed by the SPC to be faulty.
SMS Enable
Tick this checkbox to enable the SMS feature on the system.
Note: The SMS operates using a standard protocol that is used in SMS telephones.
Please note that some PSTN operators do not provide the service of SMS over
PSTN. For SMS to operate over PSTN the following criteria is required:
Caller ID needs to be enabled on the telephone line.
Direct telephone line not through PABX or other comms equipment.
Please also note that most Service Providers only allow SMS to a telephone
registered in the same country (this is due to billing issues).
SIM PIN
Only for GSM. Enter the PIN for the SIM card installed in the GSM module.
SMS Server
Number
Only for PSTN. Enter the phone number of the SMS service provider that is
accessible in your location (see table below for PSTN).
Test SMS
Click this button to send a short text message for the purposes of testing the
system.
Note: The SMS test is provided only for the purpose of ensuring the SMS feature is
operating correctly. A short text message using alphabetic characters (A-Z) should
be used to test this feature.
Automated SMS
Select the timing for automated SMS messages.
Automated SMS
#
Enter SMS number to receive automated SMS messages.
The SMS test is provided only for the purpose of ensuring the SMS feature is
operating correctly. A short text message using alphabetic characters (A-Z)
should be used to test this feature.
When using the SMS message feature over a PSTN line, it is necessary to
program the phone number of the SMS service provider that services the area in
which the SPC is installed. The SPC system automatically dials this number to
contact the SMS server whenever the SMS feature is activated. Calling line identity
MUST be enabled on the PSTN line for this feature to operate. Each country will
have its own SMS service provider with a unique phone number.
This feature is not released in all countries. Please contact your local supplier for
more information (support of feature, recommended service provider).