Engineer programming via the keypad
indicate a full set condition. (0 – 10 seconds)
The Final Exit time is the number of seconds that arming is
delayed after a zone programmed with the final exit attribute
is closed. (1 – 45 seconds)
Number of seconds to delay triggering of tech. zones with
tech. delay attribute. (0 – 9999 seconds)
Number of seconds to display fail to set message on keypads
(0 until valid PIN is entered). (0 – 999 seconds)
Note: Only available when Security Grade is
‘Unrestricted’ and ‘DD243’ is selected for ‘Confirmation’
variable. (See System Options [➙ 154])
This timer applies to the alarm confirmation feature and is
defined as the maximum time between alarms from two
different non overlapping zones that will cause a confirmed
alarm. (30 – 60 minutes)
The time period allowed for the user to exit the building after
setting the system. The exit time will be counted down at the
keypad as the buzzer beeps to indicate to the user that the
system will arm when the exit timer reaches zero.
The time period allowed for the user to UNSET the alarm
after opening an entry/exit zone of an armed system.
This attribute only applies to Remote Maintenance. The
number of hours a zone must open within if the zone is
programmed with the Frequent use attribute. (1 – 9999 hours)
Fire Pre-alarm
FIRE PRE-ALARM
Number of seconds to wait before reporting file alarm for
zones with ‘Fire pre-alarm’ attribute set. (1 – 999 seconds)
See Editing a Zone [➙ 165].
Fire recognition
FIRE RECOGNITION
Extra time to wait before reporting file alarm for zones with
‘Fire pre-alarm’ and ‘Fire Recognition’ attributes set. (1 – 999
seconds) See Editing a Zone [➙ 165].
Time after a reported alarm in which an alarm abort message
can be reported. (0 – 999 seconds))
Seismic Test Interval
SEISMIC AUTOTEST
The average period between seismic sensor automatic tests
(12 – 240 hours)
Note: To enable automatic testing, the Automatic Sensor Test
attribute must be enabled for a seismic zone.
Seismic Test Duration
SEISMIC TEST DUR
Maximum time (in seconds) that a seismic sensor takes to
trigger an alarm in response to the 'Seismic Test' output.
(3 - 120 seconds)
The time that the RF output will remain active on the system.
(0 – 999 seconds)
Time Sync Limit
TIME SYNC LIMIT
Time synchronisation only takes place if system time and
update time are outside this limit.