NCK alarms/ISO alarms
06/2007 Overview of alarms
2-137
" Siemens AG 2007 All Rights Reserved
SINUMERIK 802D sl, Diagnostics Manual, 06/2007Edition
14420 Channel %1 block %2 index axis %3 frame not allowed
Parameters: %1 = Channel number
%2 = Block number, label
%3 = Axis
Definitions: The axis is to be traversed as an indexing axis, but a frame is active. This is not allowed by machine
data FRAME_FOR_CORRPOS_NOTALLOWED.
Reaction: Correction block is reorganized.
Interface signals are set.
Alarm display.
Remedy: Please inform the authorized personnel/service department. Modify part program. Change machine
data CORR_OR_AXIS_NOT_ALLOWED.
Program Con-
tinuation:
Clear alarm with NC START or RESET key and continue the program.
14430 Channel %1 block %2 tangential axis %3 must not be traversed as POS
axis
Parameters: %1 = Channel number
%2 = Block number, label
%3 = Axis name
Definitions: A tangential corrected axis cannot be traversed as positioning axis.
Reaction: Correction block is reorganized.
Interface signals are set.
Alarm display.
Remedy: Change the part program, use TANGDEL to delete the active tangential control.
Program Con-
tinuation:
Clear alarm with NC START or RESET key and continue the program.
14432 Channel %1 block %2 rounding length for tangential axis %3 is zero.
Parameters: %1 = Channel number
%2 = Block number, label
%3 = Axis name
Definitions: A smoothing length for the activation of the tangential control with TANGON() for a tangential axis cou-
pled in the preparation, otherwise any discontinuities of the tangential axis cannot be smoothed.
Reaction: Correction block is reorganized.
Interface signals are set.
Alarm display.
Remedy: Change part program
Program Con-
tinuation:
Clear alarm with NC START or RESET key and continue the program.
14434 Channel %1 block %2 rel. lift-off path for tangential axis %3 is invalid
Parameters: %1 = Channel number
%2 = Block number, label
%3 = Axis name
Definitions: The factor r for the relative lift-off path programmed for TLIFT must lie in the range 0 =< r < 1.
Reaction: Correction block is reorganized.
Interface signals are set.
Alarm display.
Remedy: Change part program
Program Con-
tinuation:
Clear alarm with NC START or RESET key and continue the program.
14500 Channel %1 block %2 illegal DEF or PROC instruction in the part
program
Parameters: %1 = Channel number
%2 = Block number, label