NCK alarms
06/2009 Overview of alarms
2-173
© Siemens AG 2009 All Rights Reserved
SINUMERIK 802D sl, Diagnostics Manual, 06/2009
Remedy: Correct NC part program. Create the zero mark synchronization by positioning, by rotation (at least 1
revolution) in speed control mode or G74 before switching the alarm generating function on.
Program Con-
tinuation:
Clear alarm with the Delete key or NC START.
22060 [Channel %1: ] Position control expected for axis/spindle %2
Parameters: %1 = Channel number
%2 = Axis name, spindle number
Definitions: The programmed coupling type (DV, AV) or the programmed function requires position control.
Reaction: Alarm display.
Remedy: Activate position control, e.g. by programming SPCON.
Program Con-
tinuation:
Alarm display showing cause of alarm disappears. No further operator action necessary.
22062 [Channel %1: ] Axis %2 reference point approach: zero marker search
velocity (MD) is not reached
Parameters: %1 = Channel number
%2 = Axis name, spindle number
Definitions: The configured zero marker search velocity is not reached.
Reaction: NC Start disable in this channel.
Interface signals are set.
Alarm display.
NC Stop on alarm.
Remedy: Please inform the authorized personnel/service department.
Check active spindle speed limitations. Configure a lower zero marker search velocity MD34040
$MA_REFP_VELO_SEARCH_MARKER. Check the tolerance range for the actual velocity MD35150
$MA_SPIND_DES_VELO_TOL. Set a different referencing mode MD34200
$MA_ENC_REFP_MODE != 7.
Program Con-
tinuation:
Clear alarm with the RESET key. Restart part program
22064 [Channel %1: ] Axis %2 reference point approach: zero marker search
velocity (MD) is too high
Parameters: %1 = Channel number
%2 = Axis name, spindle number
Definitions: The configured zero marker search velocity is too high. The encoder limit frequency is exceeded for
the active measuring system.
Reaction: NC Start disable in this channel.
Interface signals are set.
Alarm display.
NC Stop on alarm.
Remedy: Please inform the authorized personnel/service department.
Configure a lower zero marker search velocity MD34040 $MA_REFP_VELO_SEARCH_MARKER.
Check the encoder frequency configuration MD36300 $MA_ENC_FREQ_LIMIT and MD36302
$MA_ENC_FREQ_LIMIT_LOW. Set a different referencing mode MD34200
$MA_ENC_REFP_MODE=7.
Program Con-
tinuation:
Clear alarm with the RESET key. Restart part program
22100 [Channel %1: ] Block %3 spindle %2 chuck speed exceeded
Parameters: %1 = Channel number
%2 = Axis name, spindle number
%3 = Block number, label
Definitions: The actual spindle speed is higher than the maximum speed configured in MD35100
$MA_SPIND_VELO_LIMIT plus a tolerance of 10 percent (fixed setting).
The alarm should not occur after correct optimization of the drive actuator and gear configuration.
This alarm can be reconfigured with MD11412 $MN_ALARM_REACTION_CHAN_NOREADY (chan-
nel not ready to operate) to 'BAG not ready'.
Note: Reconfiguring affects all alarms with alarm response 'Chan not ready'.
Reaction: Mode group not ready.