PROFIBUS alarms
06/2009 Overview of alarms
2-285
© Siemens AG 2009 All Rights Reserved
SINUMERIK 802D sl, Diagnostics Manual, 06/2009
If no inconsistencies can be found in the parameters, compare these machine data with the configu-
ration in SDB (STEP 7 project). In particular, check that the lengths configured for the individual slots
do not result in area overlaps. When you find the cause of the error, change the machine data and/or
SDB.
Program Con-
tinuation:
Switch control OFF - ON.
380051 PROFIBUS/PROFINET: Multiple assignment of outputs on address %1
Parameters: %1 = Logical address
Definitions: Multiple assignments of input data have been detected in the logical address space. Logical address:
Base address of the address area defined several times
Reaction: Channel not ready.
NC Start disable in this channel.
Interface signals are set.
Alarm display.
Remedy: The address partitioning should be checked as follows:
Check for multiple assignments in the following machine data:
- MD13050 $MN_DRIVE_LOGIC_ADDRESS[0] - MD13050 $MN_DRIVE_LOGIC_ADDRESS [n-1]
: n = highest axis index on control system
- MD12974 $MN_PLC_DIG_OUT_LOGIC_ADDRESS, MD12975 $MN_PLC_DIG_OUT_NUM : PLC
address area for digital outputs
- MD12982 $MN_PLC_ANA_OUT_LOGIC_ADDRESS, MD12983 $MN_PLC_ANA_OUT_NUM :
PLC address area for analog outputs
If no inconsistencies can be found in the parameters, compare these machine data with the configu-
ration in the SDB (STEP 7 project). In particular, check that the lengths configured for the individual
slots do not result in area overlaps. When you find the cause of the error, change the machine data
and/or SDB.
Program Con-
tinuation:
Switch control OFF - ON.
380060 PROFIBUS/PROFINET: Alarm %1 on logical address %2 from unassigned
slave/device
Parameters: %1 = Alarm class
%2 = Logical address
Definitions: SDB contains a slave/device which is not assigned in the NC via the MD parameters (see also alarm
380050/051). The slave/device is however connected to the PROFIBUS/PROFINET, and has
reported an alarm.
Alarm class:
- 01 = Station return (or arrival)
- 02 = Station failure
Display alarm, further operation with the NC is possible.
Reaction: Alarm display.
Remedy: - Enter machine data or
- Modify SDB or
- Disconnect the slave/device from the PROFIBUS/PROFINET or
- Acknowledge the alarm.
Program Con-
tinuation:
Clear alarm with the Delete key or NC START.
380070 PROFIBUS/PROFINET: No input slot available for basic address %1
(length %2)
Parameters: %1 = Logical base address of the requested area
%2 = Size of the area in bytes
Definitions: An incorrect logical base address was specified for a digital or analog input. Either no slot has been
configured for this base address or the requested area extends beyond the end of the slot.
Length=1 indicates a digital input.
Length=2 indicates a analog input.
Reaction: Channel not ready.
NC Start disable in this channel.
Interface signals are set.
Alarm display.