Overview of alarms 06/2009
PROFIBUS alarms
2-284
© Siemens AG 2009 All Rights Reserved
SINUMERIK 802D sl, Diagnostics Manual, 06/2009
380040 PROFIBUS/PROFINET: Bus %3, configuration error %1, parameter %2
Parameters: %1 = Cause of the error
%2 = Parameter
%3 = Number of the affected bus
Definitions: The PROFIBUS/PROFINET was not generated in the SDB in accordance with the configuration spec-
ifications of the NC in use.
Overview: Cause of the error, Par 1:
- 01 = SDB contains slave/device without diagnostics slot, slave/device address
- 02 = SDB contains too many slot entries, identifier
- 03 = SDB contains no equidistance data, no function.
- 04 = PNIO: SDB contains different Tdp (also TDC) on a device
- 05 = PNIO: SDB contains different Tmapc (also CACF) on a device
- 06 = PNIO: SDB contains different TI on a device
- 07 = PNIO: SDB contains different TO on a device
- 08 = PNIO: SDB contains device numbers that are too high (with values higher than 126)
- 09 = SDB contents are transferred segmented (too many slots/frames)
- 20 = SDB contains too many slaves/devices, quantity.
- 21 = SDB missing or contains invalid data, error code.
- 22 = SDB configuration data incorrect, slave/device address, error code
- 23 = Reserved
- 24 = Reserved
- 25 = Reserved
- 26 = Reserved
- 27 = Reserved
- 28 = Reserved
- 29 = Reserved
Reaction: Channel not ready.
NC Start disable in this channel.
Interface signals are set.
Alarm display.
Remedy: Check that the corresponding SDB
- Contains a diagnostic slot for every slave/device, and
- Contains only slave/device entries relevant to the application.
In general, it is possible to include a superset of slaves/device in the SDB that are partially relevant
for different end versions of the product. However, this overloads the NC memory and runtime capac-
ity, and should therefore be avoided in general.
If this alarm occurs, it is necessary to reduce the SDB to a minimum.
If the code for the error cause is 03, check that equidistance is activated in the SDB (e.g. using STEP
7 HW config).
If the alarm continues to occur, please send the error text to the control system manufacturer.
Program Con-
tinuation:
Switch control OFF - ON.
380050 PROFIBUS/PROFINET: Multiple assignment of inputs on address %1
Parameters: %1 = Logical address
Definitions: Multiple assignments of input data have been detected in the logical address space. Logical address:
Base address of the address area defined several times
Reaction: Channel not ready.
NC Start disable in this channel.
Interface signals are set.
Alarm display.
Remedy: The address partitioning should be checked as follows:
Check for multiple assignments in the following machine data:
- MD13050 $MN_DRIVE_LOGIC_ADDRESS[0] - MD13050 $MN_DRIVE_LOGIC_ADDRESS[n-1] :
n = highest axis index on control system
- MD12970 $MN_PLC_DIG_IN_LOGIC_ADDRESS, MD12971 $MN_PLC_DIG_IN_NUM : PLC
address area for digital inputs
- MD12978 $MN_PLC_ANA_IN_LOGIC_ADDRESS, MD12979 $MN_PLC_ANA_IN_NUM : PLC
address area for analog inputs